General
AMC series AC ammeter, adopting AC sampling technology, can directly measure current of three phase grid. It can be used for local display, and connecting industrial control device to form measuring control system.
Parameters
Communication RS485(Modbus-RTU) Display LCD display, set multiplying power Rated U & I AC current: AC1A, 5A Accuracy Active energy: Class 0.5 Installation Panel mounted |
|
Technical Datasheet
Technical Parameter | Value | |
Input | Rated Value | Single phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; |
Overload | Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second Current:1.2 times rated value(continuous); 10 times rated value /1 second | |
Frequency | 45Hz~65Hz | |
Power Consumption | Power consumption of each voltage,current input circuit is less than 0.5VA | |
Accuracy | Class 0.5 | |
Function | Display | LED or LCD |
Communication | RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps etc. | |
Alarm | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. | |
Analog | DC4~20mA,( load <500Ω) (note:Shielded wire is specially selected for the above signal input and output) | |
Switching | Input:4 channel or 2 channel dry contact Input,built in power supply Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC | |
Auxiliary Supply | AC/DC 85-265V | |
Power Consumption | <5VA | |
Insulation resistance | ≥ 100MΩ | |
Power frequency withstand voltage | Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS) Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | |
Environment | Temperature | Operation: -10℃~+55℃Storage: -25°C ~+70°C |
Humidity | ≤95%RH,no condensation,without corrosive gas | |
Altitude | ≤ 2500m |
Dimension
Wiring
Network
Installation
FAQ
Q: No display on power?
A: Check whether the supply voltage is within the operating voltage range.
Q: Incorrect reading of voltage,current,electricty,etc?
A: Checking that the voltage/current ratio setting are correct;
Checking whether the wiring mode setting is consistent with the actual situation;
Checking whether the voltage transformer and current transformer are in good condition.
Q: Abnormal communication?
A: Check whether the adress,baud rate,check bits in the communication;
Setting are consistent with the host computer;
Check whether the RS485 converter is normal;
Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.
Package
MINIMUM PACKAGE | ||||
MINIMUM PAKAGE | Package dimensions(1 PC) 170*150*130mm | Pakage Weight(1 PC) 0.62Kg | ||
WHOLE BOX PAKAGE | Package dimensions(16 PCS) 450*245*200mm | Pakage Weight(16 PCS) 3.66kG | ||
PRODUCT HS CODE | 9028301400 |
ATTENTION ! The above packing and weight data are only refer to model AMC48-AI. For other models or optional functions, please contact the salesman for details, thank you for your cooperation! |
Would you like to get information about Acrel? We appreciate your interest and would be happy to advise you.Simply give us some information so we can get in touch with you